Savolture Technical Guide
20kWh Battery: Capacity Ladder, Runtime and Inverter Sizing
Searching for a 20 kWh battery returns two kinds of result: product listings for single units that are not actually 20 kWh, and articles that calculate how long 20 kWh lasts wit...
Searching for a 20 kWh battery returns two kinds of result: product listings for single units that are not actually 20 kWh, and articles that calculate how long 20 kWh lasts without telling you what 20 kWh is built from. Neither answers the question a buyer at this stage is actually asking, which is narrower: what does a 20 kWh bank consist of, how much of it can I really use, and what inverter does it need?
This guide answers those three. It gives the capacity ladder from 5 kWh to 50 kWh with the module configuration behind each rung, the arithmetic that turns a nameplate figure into delivered energy, and the inverter sizing that decides what you can run at once. Written from the battery supply side, which is disclosed rather than hidden.
Capacity at a glance
| Question | Short answer |
|---|---|
| Is 20 kWh one battery? | No — typically 2 modules |
| Standard module voltage | 51.2 V (48 V nominal class) |
| Common module sizes | 5.12 / 10.24 / 14.34 / 16.08 kWh |
| Daily depth of discharge | 80% (90–95% is the technical limit) |
| Delivered from 20.48 kWh nameplate | ~14–15 kWh |
| What sets simultaneous load | Inverter kW, not battery kWh |
Module capacities are nameplate figures at 51.2 V. Delivered energy depends on your depth-of-discharge setting and system round-trip efficiency; the arithmetic is given below so you can run it for any capacity.

Nameplate, usable, delivered: three different numbers
Direct answer: Multiply nameplate capacity by your depth-of-discharge setting, then by system round-trip efficiency. At 80% DoD and 90% round-trip, a 20.48 kWh nameplate bank delivers about 14.7 kWh per cycle.
= Nameplate kWh × Depth of discharge × Round-trip efficiency20.48 × 0.80 × 0.90 ≈ 14.7 kWh
| Layer | What it is | Typical value | Who sets it |
|---|---|---|---|
| Nameplate | The figure on the spec sheet and the invoice | 20.48 kWh | The manufacturer |
| Usable | Nameplate minus the reserve you keep for cycle life | ~16.4 kWh at 80% DoD | Your settings, within BMS limits |
| Delivered | What reaches your loads after conversion losses | ~14.7 kWh at 90% RTE | The inverter and system design |
LFP chemistry tolerates deeper discharge than older chemistries, and 90 to 95% is within technical limits for occasional use. The reason to plan at 80% for daily cycling is cycle life: shallower daily cycles buy years. Run the deeper discharge when you need it in an outage, not as your everyday setting. We cover what actually governs cycle life in how long LiFePO4 batteries last.
Why published usable-capacity figures disagree
Direct answer: Other guides put the usable energy of a 20 kWh system anywhere from 12 kWh to 19 kWh. The spread is not disagreement about the batteries — it is that each source stops at a different point in the chain, and most do not say which point.
| What a source reports | Typical published figure | What it includes | What it leaves out |
|---|---|---|---|
| Usable at deep discharge | 18–19 kWh | Nameplate × 90–95% DoD | Round-trip losses; assumes daily deep cycling |
| Usable at conservative DoD | ~16 kWh | Nameplate × 80% DoD | Round-trip losses |
| Delivered to loads (used here) | ~14.7 kWh | Nameplate × 80% DoD × 90% RTE | Temperature effects; degradation over years |
| Conservative delivered | 12–14 kWh | Adds a larger reserve or lower efficiency assumption | — |
All four are defensible. A figure of 18 to 19 kWh is genuinely available from the pack if you discharge to 90–95% every day, and LFP tolerates that within technical limits. We plan at the third row for two reasons, and both are worth stating because they make our number look worse than the alternatives.
First, daily deep cycling costs cycle life. Reserving 20% is what turns a datasheet cycle count into years of service, so we treat 90–95% as the outage setting rather than the everyday one. Second, round-trip losses are real and they happen after the battery: energy that leaves the cells still has to pass through conversion before it reaches an appliance. A number that excludes them describes what the battery can release, not what your fridge receives.
If you are comparing quotes or articles, the useful move is not to pick the biggest number but to ask which of these four each source is quoting, then recompute them all on the same basis with the formula above.
The Capacity Ladder: what each tier is built from
Direct answer: At 51.2 V, common modules are 100 Ah (5.12 kWh), 200 Ah (10.24 kWh), 280 Ah (14.34 kWh) and 314 Ah (16.08 kWh). Nearly every residential target is a combination of these, which is why real bank sizes land on 20.48 or 30.72 rather than a round 20 or 30.
| Target | Typical build at 51.2 V | Nameplate | Delivered (80% DoD, 90% RTE) | Typical buyer | Not sufficient alone for |
|---|---|---|---|---|---|
| 5 | 1 × 100 Ah | 5.12 kWh | ~3.7 kWh | Essential circuits, cabin, budget entry | Central air, well pump, whole-home |
| 10 | 1 × 200 Ah | 10.24 kWh | ~7.4 kWh | Partial-home backup, overnight self-consumption | Multi-day outage without solar recharge |
| 15 | 1 × 280 Ah | 14.34 kWh | ~10.3 kWh | Larger partial backup, EV-owning household | Running everything at once — see inverter limits |
| 16 | 1 × 314 Ah | 16.08 kWh | ~11.6 kWh | Highest single-module density | Same as above; capacity is not power |
| 20 | 2 × 200 Ah | 20.48 kWh | ~14.7 kWh | Typical whole-home daily cycling | Extended off-grid autonomy |
| 30 | 3 × 200 Ah | 30.72 kWh | ~22.1 kWh | Large home, heavy loads, partial off-grid | Full off-grid through poor solar weeks |
| 32 | 2 × 314 Ah | 32.16 kWh | ~23.2 kWh | Same as above, fewer enclosures | Same |
| 40 | 4 × 200 Ah | 40.96 kWh | ~29.5 kWh | Off-grid property, light commercial | Sites needing multi-day autonomy in winter |
| 50 | 5 × 200 Ah or 3 × 314 Ah | 51.2 / 48.24 kWh | ~36.9 / ~34.7 kWh | Off-grid, commercial, project volume | Grid-scale applications |
Delivered figures use 80% depth of discharge and 90% round-trip efficiency for consistency; substitute your own values with the formula above. Capacity options are covered on our 48V LiFePO4 systems page.
Two things fall out of this table. First, 20 kWh is not a product, it is two 200 Ah modules — which is why searching for a single 20 kWh unit returns so little. Second, the same target can often be reached two ways: 32 kWh is either two 314 Ah modules or three 200 Ah modules, and the choice comes down to wall space, per-module cost and how you plan to expand later.
What a 20 kWh bank costs, and why the per-kWh figure matters more
Direct answer: Published installed pricing for a 20 kWh LFP bank runs roughly $700 to $800 per kWh, or about $14,000 to $16,000 all-in, with the upper end applying when the system needs its own inverter rather than working with one you already have. Compare on cost per kWh rather than total, because the totals describe different capacities.
| Scenario | Published installed cost | Per kWh | What drives it |
|---|---|---|---|
| 20 kWh bank, existing inverter usable | ~$13,900 | ~$696 | Modules, BMS, labour, basic integration |
| 20 kWh bank, new inverter required | ~$16,100 | ~$806 | Adds AC-coupled inverter and its install |
| Reference: sealed 13.5 kWh unit | ~$13,000–16,600 | ~$963–1,230 | Higher per kWh; includes integrated inverter |
Figures compiled from published installer and review pricing, not from our own quotations. Installed cost varies substantially by market, site condition and installer — treat these as planning ranges. The sealed-unit reference row is included because it is the comparison most buyers are actually making.
Two things are worth reading out of that table. The first is that the inverter question moves the number by roughly $100 per kWh, which is why “do I already own a working inverter” belongs in the first conversation rather than the last. The second is that a modular LFP bank generally lands below a sealed all-in-one on a per-kWh basis, largely because the sealed product bundles an inverter into every unit. Whether that is the better buy depends on what you value — we set out the trade honestly in our breakdown of what home storage actually costs.
One caution on scaling the arithmetic: cost per kWh is not flat across the ladder. Smaller banks carry a higher per-kWh figure because fixed costs (labour, permitting, enclosure, protection) are spread over less capacity. A 5 kWh install is not a quarter the price of a 20 kWh install.
What has to be true for a bank to work
Direct answer: A working bank needs matched modules, a compatible inverter, correct conductor sizing, and a communication path between the battery management system and the inverter. Missing any one of them produces a system that is either unsafe, under-performing, or silent.
| # | Component | Function | Key spec | What fails without it |
|---|---|---|---|---|
| 01 | Matched modules | Share charge and discharge evenly across the bank | Same model, ideally same firmware revision | Mismatched modules fight each other; one ages faster |
| 02 | Hybrid inverter | Converts DC to AC and sets simultaneous load capability | Continuous kW rating, 48 V class input | Capacity you cannot draw at the rate you need it |
| 03 | BMS communication | Lets the inverter read state of charge and limits | CAN or RS485, protocol matched | Open-loop operation; charge limits not managed by the pack |
| 04 | Conductors and protection | Carry bank current safely | Sized to maximum discharge current | Voltage drop, heat, inspection failure |
| 05 | Enclosure and siting | Keeps modules within operating temperature | Indoor or rated outdoor location | Cold-weather charge limiting; accelerated ageing |
Item 03 is the one most often discovered late. A bank that charges is not proof that the inverter is reading the battery — that agreement has to be verified at commissioning. Our inverter and battery compatibility hub covers what closed-loop pairing requires, and conductor sizing for the current your bank can actually deliver is covered in the 48V cable size chart.

The Inverter Ceiling
Direct answer: Size the battery to your daily energy in kWh and the inverter to your simultaneous load in kW. These are independent decisions and buyers routinely get the first right and the second wrong.
| Inverter continuous rating | What it realistically runs together | Pairs with | Not sufficient alone for |
|---|---|---|---|
| ~5 kW | Lights, outlets, fridge, networking, a small pump | 5–10 kWh banks | Central air, electric range, well pump start surge |
| ~8 kW | The above plus one large appliance at a time | 10–20 kWh banks | Several large loads simultaneously |
| ~12 kW+ | Most whole-home scenarios without load management | 20 kWh and above | Off-grid sites with heavy motor starting |
The mismatch shows up in a specific way: the system runs fine for weeks, then trips the first time the air conditioner and the oven come on together. That is not a battery fault and adding capacity will not fix it. If you are still choosing, our hybrid inverter page covers the pairing side, and the off-grid battery calculator works the capacity half.
How long will 20 kWh actually last?
Direct answer: Divide delivered energy by your average load. A 20.48 kWh bank delivering about 14.7 kWh runs roughly 7 hours at a steady 2 kW, or covers a full day for a household using 10 to 15 kWh — the typical range for a US home of three to five people.
| Scenario | Average draw | Runtime from ~14.7 kWh | Note |
|---|---|---|---|
| Essential circuits only | 0.5 kW | ~29.4 hours | Fridge, lights, networking, phone charging |
| Partial home | 1 kW | ~14.7 hours | Adds a few larger circuits |
| Typical whole home | 2 kW | ~7.4 hours | Overnight coverage for most homes |
| Heavy simultaneous load | 4 kW | ~3.7 hours | Requires an inverter that can supply 4 kW |
Runtime figures assume the delivered energy calculated above. Actual results vary with load profile, temperature and settings — treat these as planning arithmetic, not guarantees.
The last row is where the two ceilings meet: drawing 4 kW is only possible if the inverter is rated for it, regardless of how much capacity sits behind it.
Building the number from your own appliances
Aggregate figures are only useful once you can assemble one. The table below gives typical residential consumption so you can build a daily total rather than guess at it — and, in the right-hand column, the running draw that determines whether your inverter can carry the load at all.
| Load | Typical daily energy | Running draw | Sizing note |
|---|---|---|---|
| Refrigerator | 1.5–2.5 kWh | ~0.15 kW | Cycles on and off; low draw, runs all day |
| LED lighting | 1–2 kWh | ~0.1 kW | Negligible for inverter sizing |
| Wi-Fi, networking, standby | 0.3–0.6 kWh | ~0.03 kW | Small but continuous |
| Furnace blower fan | 1.5–2.0 kWh | ~0.5 kW | Essential in winter; often overlooked |
| Electric oven | 2.5–4.5 kWh per hour of use | ~2.4 kW | Short bursts, high draw |
| Central air conditioning | 3–5 kWh per hour of use | ~3–4 kW | The load that most often exceeds the inverter, not the battery |
Typical residential ranges for planning. Actual consumption varies with appliance age, efficiency rating, climate and usage pattern — your utility bill is a better source than any table for the daily total.
Add the daily figures for what you intend to back up and compare the total against delivered energy; add the running draws for what might run simultaneously and compare that against the inverter rating. Most homes clear the first test at 20 kWh and fail the second if the inverter was chosen carelessly.
How much solar recharges a 20 kWh bank?
Direct answer: To put back the roughly 16.3 kWh a 20.48 kWh bank consumes in a full cycle, you need about 4.5 kW of array in a location averaging 4.5 peak sun hours. Lower-sun sites and winter months need more; the array does not scale with battery capacity but with the energy you actually cycle through it.
= (Delivered kWh ÷ Round-trip efficiency) ÷ (Peak sun hours × Derate)(14.7 ÷ 0.90) ÷ (4.5 × 0.80) ≈ 4.5 kW
| Site condition | Peak sun hours | Array to recharge ~16.3 kWh | Note |
|---|---|---|---|
| Lower sun or winter months | 3.5 | ~5.8 kW | Size for the worst season if you need year-round autonomy |
| Typical US annual average | 4.5 | ~4.5 kW | Reasonable planning default |
| High-sun region | 5.5 | ~3.7 kW | Annual average flatters winter performance |
A 0.80 derate covers soiling, temperature, wiring and inverter losses. Figures assume the entire array output goes to the battery, which it does not in practice — daytime loads are served first, so a grid-tied system needs less array than this to keep the bank cycling.
The seasonal point matters more than the average. An array sized to the annual mean will recharge the bank comfortably in summer and fall short in December, which is why off-grid designs size to the worst month and grid-tied designs do not have to. Off-grid sizing is covered in our off-grid solar systems guide.
The 5 sizing mistakes
Direct answer: Five errors account for most banks that disappoint their owners, and four of them happen before anything is installed.
| # | Mistake | What it causes | Fix | Not sufficient alone |
|---|---|---|---|---|
| 01 | Sizing on nameplate capacity | Bank delivers roughly 70% of the expected energy | Plan on delivered energy using the formula | Delivered energy still varies with temperature |
| 02 | Sizing capacity but not the inverter | Runs for hours, but trips on simultaneous loads | Size kW to peak simultaneous draw separately | Motor starting surge exceeds continuous rating |
| 03 | Planning daily cycling at maximum depth | Cycle life shortened for capacity rarely needed | Plan daily at 80%; keep deeper discharge for outages | Cycle life also depends on temperature |
| 04 | Mixing module models or revisions | Uneven ageing; the weakest module governs | Match model and revision across the bank | Confirm the supplier’s parallel limit for that model |
| 05 | Assuming the inverter reads the battery | Open-loop operation; limits unmanaged | Verify state of charge agrees on both devices | Charging normally is not proof of communication |
When a bigger bank is the wrong answer
Direct answer: Above roughly 30 kWh, adding capacity stops solving the common residential problems. If your issue is tripping on simultaneous loads, buy inverter capacity. If it is multi-day autonomy, add generation or a generator. If it is cost per kWh, buy fewer, larger modules rather than more small ones.
We supply batteries, so this is the section where we argue against selling more of them. Three situations where capacity is not the fix:
| Symptom | What buyers add | What actually fixes it |
|---|---|---|
| System trips when two large appliances run together | More kWh | A higher continuous kW inverter, or load management |
| Bank empty by morning in winter | More kWh | More generation, or a generator for the shoulder days |
| Cost per kWh feels high | More small modules | Fewer, larger modules — fixed costs spread wider |
| Genuinely need multi-day autonomy off-grid | — | More capacity is correct here |
The third row deserves emphasis because it runs against the modular instinct: four 100 Ah modules and one 200 Ah module reach similar capacity, but the smaller build costs more per kWh in enclosures, wiring and labour. Modularity is worth paying for when you genuinely intend to expand in stages, and worth avoiding when you already know the final size.
What is changing in 2026
Direct answer: Two shifts matter for capacity planning: module energy density has risen so single modules now reach 16 kWh where 5 kWh was standard, and the federal Section 25D credit ended for homeowner cash and loan purchases after 31 December 2025, which changes how buyers weigh a larger bank.
The density change is the quieter one and it alters the ladder. A 32 kWh bank that once meant six modules is now two, which reduces wall space, wiring runs and installation labour. If you are comparing quotes built on different module sizes, the per-kWh hardware price is only part of the difference — the install cost differs too.
The incentive change pushes the other way. Without a 30% federal credit on a purchased system, the marginal cost of extra capacity is fully out of pocket, which makes the “size it properly rather than generously” discipline worth more than it was. That makes the discipline of sizing to measured load, rather than to a round number, worth more than it was a year ago.
1. Looking for a single 20 kWh battery
Wrong: assuming 20 kWh is a product. Right: it is a bank — typically two 200 Ah modules at 51.2 V, totalling 20.48 kWh nameplate.
2. Comparing nameplate against delivered
Wrong: comparing one supplier’s nameplate to another’s usable figure. Right: convert both to delivered energy with the same DoD and efficiency assumptions.
3. Buying capacity to solve a power problem
Wrong: adding kWh because the system tripped. Right: tripping is an inverter kW limit; capacity does not touch it.
4. Sizing from a guess rather than a bill
Wrong: picking 20 kWh because it sounds sufficient. Right: use twelve months of utility data for the average and the worst day.
5. Ignoring the parallel limit
Wrong: assuming you can keep adding modules indefinitely. Right: the battery’s BMS sets a maximum parallel count; ask for it before designing a large bank.
6. Treating round numbers as available sizes
Wrong: specifying “30 kWh” and expecting an exact match. Right: real builds land on 30.72 or 32.16; design around the module step.
Frequently asked questions
Is a 20 kWh battery a single unit?
Rarely. At 51.2 V the common residential build is two 200 Ah modules totalling 20.48 kWh nameplate. Single modules in this class typically range from 5.12 kWh to 16.08 kWh, so a 20 kWh target is reached by combining modules rather than buying one large unit.
How long will a 20 kWh battery last?
After an 80% depth of discharge and roughly 90% round-trip efficiency, a 20.48 kWh bank delivers about 14.7 kWh per cycle. That is around 7 hours at a steady 2 kW draw, about 29.4 hours on essential circuits only at 0.5 kW, or roughly a full day for a household using 10 to 15 kWh.
How much usable capacity does a 20 kWh battery have?
About 16.4 kWh usable at an 80% depth of discharge, of which roughly 14.7 kWh reaches your loads after conversion losses. LFP chemistry tolerates 90 to 95% discharge within technical limits, but planning daily cycling at 80% preserves cycle life.
What size inverter do I need for a 20 kWh battery?
That depends on simultaneous load rather than capacity. Around 8 kW continuous suits most 20 kWh residential installations, handling essentials plus one large appliance at a time; 12 kW or more is needed for whole-home operation without load management. Capacity and inverter rating are independent decisions.
How many batteries do I need for 20 kWh?
Two 200 Ah modules at 51.2 V, giving 20.48 kWh. Four 100 Ah modules reach a similar 20.48 kWh but cost more per kWh in enclosures, wiring and labour, so fewer larger modules is usually the better build unless you specifically want smaller expansion steps.
Is 20 kWh enough for a whole house?
For daily cycling, usually yes — it covers a typical household’s 10 to 15 kWh daily consumption with margin. For extended outages without solar recharge, it covers roughly one day. Whole-home operation also requires an inverter sized to your simultaneous loads, which is the more common constraint.
How much solar do I need for a 20 kWh battery?
About 4.5 kW of array in a location averaging 4.5 peak sun hours, which is enough to replace the roughly 16.3 kWh a full cycle consumes. Sites with less sun, or winter operation, need closer to 5.8 kW. Grid-tied systems need less than this because daytime loads are served directly by the array rather than through the battery.
Can I add more capacity later?
Yes, within the parallel limit set by the battery’s management system, and best done with the same model and firmware revision. Ask the supplier for the maximum parallel count for your specific model before designing a bank you intend to expand, because that limit comes from the battery rather than the inverter.
Get a configuration sized to your loads
Send these four items and we will return a specified configuration (module count, nameplate and delivered capacity, and the inverter rating it needs) rather than a brochure.
- Average daily consumption in kWh, from twelve months of utility bills if possible
- Peak simultaneous load — the circuits and appliances that must run together
- Grid-tied or off-grid, and whether solar is already installed
- Market — for the correct certification scope
Related reading
For the modules behind these tiers, see our 200Ah module (the building block of most 20 kWh banks) and the 314Ah module for higher density in fewer enclosures. Smaller builds start at the 100Ah module. For whole-home design rather than capacity alone, see the whole-home backup guide.
Why we wrote this
We supply LFP battery modules factory-direct, mostly to installers and resellers, so we see the same sizing conversation repeatedly: a buyer arrives with a capacity number and no load data, and leaves with a different configuration than they expected. We wrote the ladder and the arithmetic rather than a product page because the conversion between “how many kWh” and “which modules” is genuinely missing from what is published — capacity guides calculate runtime without giving the build, and product listings give the build without explaining the capacity. Where a figure depends on your settings or your supplier’s model, we have said so rather than publishing a single number.
Brand: Savolture · Country: China · Model: B2B factory-direct LFP storage
Products built to UL 9540 and CEC-referenced configurations · Factory audits welcome
Email: Contact us · Web: savolture.com
1. Module nameplate capacities are calculated from rated amp-hours at 51.2 V nominal: 100 Ah = 5.12 kWh, 200 Ah = 10.24 kWh, 280 Ah = 14.34 kWh, 314 Ah = 16.08 kWh.
2. Depth-of-discharge planning convention: 80% for daily cycling, with 90–95% treated as the technical limit for LFP chemistry rather than an everyday setting.
3. Round-trip efficiency of 90% used throughout as a system-level planning figure; confirm the figure published for your specific inverter and battery pairing.
4. US household daily electricity consumption of roughly 10–15 kWh for a three-to-five person home, used as the sizing reference range.
5. Published installed pricing for 20 kWh residential LFP systems, reported at approximately $696 per kWh without a new inverter and $806 per kWh with an AC-coupled inverter; sealed 13.5 kWh comparison pricing from published installed ranges divided by usable capacity.
6. Typical residential appliance consumption ranges (refrigerator, lighting, networking, furnace blower, electric oven, central air conditioning) compiled from published installer sizing guidance.
7. UL 9540 (Energy Storage Systems and Equipment) — referenced for certification scope terminology.
8. Internal Revenue Code Section 25D (Residential Clean Energy Credit), as amended by the One Big Beautiful Bill Act — termination for homeowner cash and loan purchases after 31 December 2025.
All delivered-energy and runtime figures in this article are planning arithmetic derived from the formula given, not measured results or guarantees.
Ready to size your system?
Get a free battery recommendation.
Tell us your load, location, and backup target — we will spec the right 48V LiFePO4 system for you.
